200-240V, 3-Phase: Protected Chassis/NEMA 1 | Flange | 1-Phase: Standard
380-480V, 3-Phase: Protected Chassis/NEMA 1 | Flange | 12-Pulse | 1-Phase: Standard/NEMA 1
500-600V, 3-Phase: Protected Chassis/NEMA 1 | Flange | 1-Phase: Standard

200-240V, 3-Phase, Protected Chassis/NEMA 1

Drive Model Number Standard
Normal Duty (ND)1
Heavy Duty (HD)1
Standard Enclosure
Rated Output Current (Amps)
Nominal HP2
Rated Output Current (Amps)
Nominal HP2
CIMR-AU2A0004FAA
3.5
3/4
3.2
3/4
NEMA 1
CIMR-AU2A0006FAA
6
1
5
1
CIMR-AU2A0008FAA
8
2
6.9
2
CIMR-AU2A0010FAA
9.6
2
8
2
NEMA 1
CIMR-AU2A0012FAA
12
3
11
3
CIMR-AU2A0018FAA
17.5
5
14
3
CIMR-AU2A0021FAA
21
7.5
17.5
5
NEMA 1
CIMR-AU2A0030FAA
30
10
25
7.5
CIMR-AU2A0040FAA
40
15
33
10
CIMR-AU2A0056FAA
56
20
47
15
NEMA 1
CIMR-AU2A0069FAA
69
25
60
20
CIMR-AU2A0081FAA
81
30
75
25
CIMR-AU2A0110FAA
110
40
85
30
NEMA 1
CIMR-AU2A0138FAA
138
50
115
40
CIMR-AU2A0169FAA
169
60
145
50
NEMA 1
CIMR-AU2A0211FAA
211
75
180
60
CIMR-AU2A0250AAA
250
100
215
75
Protected Chassis
CIMR-AU2A0312AAA
312
125
283
100
CIMR-AU2A0360AAA
360
150
346
125
Protected Chassis
CIMR-AU2A0415AAA 415 175 415 150
  1. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  2. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors. Also, listed power ratings assumes three-phase input. For single-phase input applications, consult Manual Supplement TOEPYEASUP03 for proper sizing.

Back to Top

200-240V, 3-Phase, Flange

Drive Model Number Flange1
Normal Duty (ND)2
Heavy Duty (HD)2
Enclosure1
Rated Output Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
CIMR-AU2A0004UAA
3.5
3/4
3.2
3/4
Flange
CIMR-AU2A0006UAA
6
1
5
1
CIMR-AU2A0008UAA
8
2
6.9
2
CIMR-AU2A0010UAA
9.6
3
8
2
Flange
CIMR-AU2A0012UAA
12
3
11
3
CIMR-AU2A0018UAA
17.5
5
14
3
CIMR-AU2A0021UAA
21
7.5
17.5
5
Flange
CIMR-AU2A0030UAA
30
10
25
7.5
CIMR-AU2A0040UAA
40
15
33
10
CIMR-AU2A0056UAA
56
20
47
15
Flange
CIMR-AU2A0069UAA
69
25
60
20
CIMR-AU2A0081UAA
81
30
75
25
CIMR-AU2A0110UAA
110
40
85
30
Flange
CIMR-AU2A0138UAA
138
50
115
40
CIMR-AU2A0169UAA
169
60
145
50
CIMR-AU2A0211UAA
211
75
180
60
Flange
CIMR-AU2A0250UAA
250
100
215
75
CIMR-AU2A0312UAA
312
125
283
100
CIMR-AU2A0360UAA
360
150
346
125
Flange
CIMR-AU2A0415UAA
415
175
415
150
  1. Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
  2. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  3. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors

Back to Top

240V, Single-Phase Input, (208-230V Three-Phase Output)

Drive Model Number 1, 2, 3
Single Phase Input - Sizing Method A (A) (continuous full power)
Single Phase Input - Sizing Method B (B) (86% max power of connected motor size)
Without Additional Reactor
With Additional Reactor
Motor Amps Motor Size (HP) Motor Amps Motor Size (HP)
Motor Amps
Motor Size (HP)
CIMR-AU2A0004FAA
1.7
1/3
2.4
1/2
2.4
1/2
CIMR-AU2A0006FAA
3.5
3/4
3.5
3/4
4.6
1
CIMR-AU2A0008FAA
4.6
1
4.6
1
4.6
1
CIMR-AU2A0010FAA
4.6
1
4.6
1
6.6
1.5
CIMR-AU2A0012FAA
6.6
1.5
7.5
2
7.5
2
CIMR-AU2A0018FAA
7.5
2
10.6
3
10.6
3
CIMR-AU2A0021FAA
7.5
2
10.6
3
10.6
3
CIMR-AU2A0030FAA
10.6
3
10.6
3
17.0
5
CIMR-AU2A0040FAA
10.6
3
17
5
17.0
5
CIMR-AU2A0056FAA
17
5
24
7.5
24.0
7.5
CIMR-AU2A0069FAA
24
7.5
31
10
31.0
10
CIMR-AU2A0081FAA
31
10
46
15
46
15
CIMR-AU2A0110FAA
31
10
31
10
46
15
CIMR-AU2A0138FAA
46
15
46
15
59
20
CIMR-AU2A0169FAA
59
20
59
20
75
25
CIMR-AU2A0211FAA
75
25
75
25
88
30
CIMR-AU2A0250AAA
88
30
88
30
114
40
CIMR-AU2A0312AAA
114
40
114
40
143
50
CIMR-AU2A0360AAA
143
50
143
50
169
60
CIMR-AU2A0415AAA
169
60
169
60
211
75
  1. Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A0081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
  2. Only models ending in FAA (CIMR-AU2A0211FAA and smaller) come standard with NEMA 1 End Cap Kits. Separately sold kits are available for larger models.
  3. For Flange Drives, use the sizing method above to determine proper drive size. Use selected model numbers with "UAA" suffix instead of "FAA" or "AAA" suffix.
  1. Use single phase input sizing method A for applications requiring more than 86% motor power. When sizing with additional reactor, consult factory. Caution: Adding more impedance than specified will degrade performance.
  2. Use single phase input sizing method B for applications requiring a maximum of 86% motor power.

Back to Top

380-480V, 3-Phase, Protected Chassis/NEMA 1

Drive Model Number Standard
Normal Duty (ND)1
Heavy Duty (HD)1
Standard Enclosure
Rated Output Current (Amps)
Nominal HP2
Rated Output Current (Amps)
Nominal HP2
CIMR-AU4A0002FAA
2.1
3/4 & 1
1.8
3/4
NEMA 1
CIMR-AU4A0004FAA
4.1
2
3.4
1 & 2
CIMR-AU4A0005FAA
5.4
3
4.8
3
CIMR-AU4A0007FAA
6.9
4
5.5
3
NEMA 1
CIMR-AU4A0009FAA
8.8
5
7.2
4
CIMR-AU4A0011FAA
11.1
7.5
9.2
5
CIMR-AU4A0018FAA
17.5
10
14.8
7.5 & 10
NEMA 1
CIMR-AU4A0023FAA
23
15
18
10
CIMR-AU4A0031FAA
31
20
24
15
CIMR-AU4A0038FAA
38
25
31
20
NEMA 1
CIMR-AU4A0044FAA
44
30
39
25 & 30
CIMR-AU4A0058FAA
58
40
45
30
CIMR-AU4A0072FAA
72
50
60
40
NEMA 1
CIMR-AU4A0088FAA
88
60
75
50 & 60
CIMR-AU4A0103FAA
103
75
91
60
CIMR-AU4A0139FAA
139
100
112
75
NEMA 1
CIMR-AU4A0165FAA
165
125
150
100
CIMR-AU4A0208AAA
208
150
180
125 & 150
Protected Chassis
CIMR-AU4A0250AAA
250
200
216
150
CIMR-AU4A0296AAA
296
250
260
200
CIMR-AU4A0362AAA
362
300
304
250
Protected Chassis
CIMR-AU4A0414AAA
414
350
370
300
CIMR-AU4A0515AAA
515
400
450
350
Protected Chassis
CIMR-AU4A0675AAA
675
500
605
400-500
CIMR-AU4A0930AAA
930
700-800
810
600-700
Protected Chassis
CIMR-AU4A1200AAA
1200
900-1000
1090
800-900
  1. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  2. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors. Also, listed power ratings assumes three-phase input. For single-phase input applications, consult Manual Supplement TOEPYEASUP03 for proper sizing.

Back to Top

380-480V, 3-Phase, Flange

Drive Model Number Flange1
Normal Duty (ND)2
Heavy Duty (HD)2
Enclosure1
Rated Output Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
CIMR-AU4A0002UAA
2.1
1
1.8
3/4
Flange
CIMR-AU4A0004UAA
4.1
2
3.4
1 & 2
CIMR-AU4A0005UAA
5.4
3
4.8
3
CIMR-AU4A0007UAA
6.9
4
5.5
3
Flange
CIMR-AU4A0009UAA
8.8
5
7.2
5
CIMR-AU4A0011UAA
11.1
7.5
9.2
5
CIMR-AU4A0018UAA
17.5
10
14.8
7.5 & 10
Flange
CIMR-AU4A0023UAA
23
15
18
10
CIMR-AU4A0031UAA
31
20
24
15
CIMR-AU4A0038UAA
38
25
31
20
Flange
CIMR-AU4A0044UAA
44
30
39
25 & 30
CIMR-AU4A0058UAA
58
40
45
30
CIMR-AU4A0072UAA
72
50
60
40
Flange
CIMR-AU4A0088UAA
88
60
75
50 & 60
CIMR-AU4A0103UAA
103
75
91
60
CIMR-AU4A0139UAA
139
100
112
75
Flange
CIMR-AU4A0165UAA
165
125
150
100
CIMR-AU4A0208UAA
208
150
180
125 & 150
Flange
CIMR-AU4A0250UAA
250
200
216
150
CIMR-AU4A0296UAA
296
250
260
200
CIMR-AU4A0362UAA
362
300
304
250
Flange
CIMR-AU4A0414UAA
414
350
370
300
CIMR-AU4A0515UAA
515
400
450
350
Flange
CIMR-AU4A0675UAA
675
500
605
400-500
CIMR-AU4A0930UAA4
930
700-800
810
600-700
Flange
CIMR-AU4A1200UAA4
1200
900-1000
1090
800-900
  1. Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
  2. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  3. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors
  4. Models CIMR-AU4A0930UAA and CIMR-AU4A1200UAA must be used with semiconductor input fuses and must be fed by a power source that has ground fault protection. A supplementary ground fault protection device can be added between the drive and the power source to address this requirement.

Back to Top

380-480V, 3-Phase,12-Pulse

Drive Model Number 12-Pulse Flange1
Normal Duty (ND)2
Heavy Duty (HD)2
Enclosure1
Rated Output Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
CIMR-AU4T0058UAA
58
40
45
30
Flange
CIMR-AU4T0072UAA
72
50
60
40
CIMR-AU4T0088UAA
88
60
75
50 & 60
Flange
CIMR-AU4T0103UAA
103
75
91
60
CIMR-AU4T0139UAA
139
100
112
75
Flange
CIMR-AU4T0165UAA
165
125
150
100
CIMR-AU4T0208UAA
208
150
180
125 & 150
Flange
CIMR-AU4T0250UAA
250
200
216
150
CIMR-AU4T0296UAA
296
250
260
200
CIMR-AU4T0362UAA
362
300
304
250
Flange
CIMR-AU4T0414UAA
414
350
370
300
CIMR-AU4T0515UAA
515
400
450
350
Flange
CIMR-AU4T0675UAA
675
500-600
605
400-500
See note 4
930
700-800
810
600-700
Fnlage
See note 4
1200
900-1000
1090
800-900
  1. Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external. Flange parts can be removed if conventional mounting is desired.
  2. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds.
  3. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors.
  4. Models CIMR-AU4A0930xxx and CIMR-AU4A1200xxx are user configurable for either 6-Pulse (3-Phase) or 12-Pulse (6-Phase) input. See Standard 480V for model numbers.>

Back to Top

480V, Single-Phase Input, (460V Three-Phase Output)

Drive Model Number 1, 2, 3
Drive Model Number (NEMA 1 Compatible)
Single Phase Input - Sizing Method A (A) (continuous full power)
Single Phase Input - Sizing Method B (B) (86% max power of connected motor size)
Without Additional Reactor
With Additional Reactor
Motor Amps Motor Size (HP) Motor Amps Motor Size (HP)
Motor Amps
Motor Size (HP)
CIMR-AU4A0002FAA
 
0.8
1/3
1.1
1/2
0.8
1/3
CIMR-AU4A0004FAA
 
1.6
3/4
2.1
1
2.1
1
CIMR-AU4A0005FAA
 
2.1
1
3.0
1.5
3.0
1.5
CIMR-AU4A0007FAA
 
3.0
1.5
3.4
2
3.4
2
CIMR-AU4A0009FAA
 
3.4
2
4.8
3
4.8
3
CIMR-AU4A0011FAA
 
3.4
2
4.8
3
4.8
3
CIMR-AU4A0018FAA
 
4.8
3
4.8
3
7.6
5
CIMR-AU4A0023FAA
 
4.8
3
7.6
5
7.6
5
CIMR-AU4A0031FAA
 
11
7.5
11
7.5
14.0
10
CIMR-AU4A0038FAA
 
11
7.5
14
10
14.0
10
CIMR-AU4A0044FAA
 
14
10
14
10
21.0
15
CIMR-AU4A0058FAA
 
21
15
21
15
27.0
20
CIMR-AU4A0072FAA
 
27
20
27
20
34.0
25
CIMR-AU4A0088FAA
 
27
20
27
20
34.0
25
CIMR-AU4A0103FAA
 
27
20
27
20
34.0
25
CIMR-AU4A0139FAA
 
52
40
52
40
65.0
50
CIMR-AU4A0165FAA
 
52
40
52
40
65.0
50
CIMR-AU4A0208AAA
 
65
50
65
50
77.0
60
CIMR-AU4A0250AAA
 
77
60
77
60
96
75
CIMR-AU4A0296AAA
 
96
75
96
75
124
100
CIMR-AU4A0362AAA
 
124
100
124
100
156
125
CIMR-AU4A0414AAA
CIMR-UUX000679
156
125
156
125
180
150
CIMR-AU4A0515AAA
CIMR-UUX000680
156
125
156
125
180
150
CIMR-AU4A0675AAA
CIMR-UUX000681
180
150
180
150
240
200
  1. Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A0081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
  2. Only models ending in FAA (CIMR-AU2A0211FAA and smaller) come standard with NEMA 1 End Cap Kits. Separately sold kits are available for larger models.
  3. For Flange Drives, use the sizing method above to determine proper drive size. Use selected model numbers with "UAA" suffix instead of "FAA" or "AAA" suffix.
  1. Use single phase input sizing method A for applications requiring more than 86% motor power. When sizing with additional reactor, consult factory. Caution: Adding more impedance than specified will degrade performance.
  2. Use single phase input sizing method B for applications requiring a maximum of 86% motor power.

Back to Top

500-600V, 3-Phase, Protected Chassis/NEMA 1

Drive Model Number Standard
Normal Duty (ND)1
Heavy Duty (HD)1
Standard Enclosure
Rated Output Current (Amps)
Nominal HP2
Rated Output Current (Amps)
Nominal HP2
CIMR-AU5A0003FAA
2.7
1 & 2
1.7
1
NEMA 1
CIMR-AU5A0004FAA
3.9
3
3.5
2
CIMR-AU5A0006FAA
6.1
5
4.1
3
CIMR-AU5A0009FAA
9
7.5
6.3
5
NEMA 1
CIMR-AU5A0011FAA
11
10
9.8
7.5
CIMR-AU5A0017FAA
17.5
15
12.5
10
CIMR-AU5A0022FAA
22
20
17
15
NEMA 1
CIMR-AU5A0027FAA
27
25
22
20
CIMR-AU5A0032FAA
32
30
27
25
CIMR-AU5A0041FAA
41
40
32
30
NEMA 1
CIMR-AU5A0052FAA
52
50
41
40
CIMR-AU5A0062FAA
62
60
52
50
CIMR-AU5A0077FAA
77
75
62
60
NEMA 1
CIMR-AU5A0099FAA
99
100
77
75
CIMR-AU5A0125AAA
125
125
99
100
Protected Chassis
CIMR-AU5A0145AAA
145
150
130
125
CIMR-AU5A0192AAA
192
200
172
150
Protected Chassis
CIMR-AU5A0242AAA
242
250
200
200
  1. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  2. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430.150 Full-Load Current, Three-Phase Alternating Current Motors. Also, listed power ratings assumes three-phase input. For single-phase input applications, consult Manual Supplement TOEPYEASUP03 for proper sizing.

Back to Top

500-600V, 3-Phase, Flange

Drive Model Number Flange1
Normal Duty (ND)2
Heavy Duty (HD)2
Enclosure1
Rated Output Current (Amps)
Nominal HP3
Rated Output Current (Amps)
Nominal HP3
CIMR-AU5A0003UAA
2.7
1 & 2
1.7
1
Flange
CIMR-AU5A0004UAA
3.9
3
3.5
2
CIMR-AU5A0006UAA
6.1
5
4.1
3
CIMR-AU5A0009UAA
9
7.5
6.3
5
Flange
CIMR-AU5A0011UAA
11
10
9.8
7.5
CIMR-AU5A0017UAA
17.5
15
12.5
10
CIMR-AU5A0022UAA
22
20
17
15
Flange
CIMR-AU5A0027UAA
27
25
22
20
CIMR-AU5A0032UAA
32
30
27
25
CIMR-AU5A0041UAA
41
40
32
30
Flange
CIMR-AU5A0052UAA
52
50
41
40
CIMR-AU5A0062UAA
62
60
52
50
CIMR-AU5A0077UAA
77
75
62
60
Flange
CIMR-AU5A0099UAA
99
100
77
75
CIMR-AU5A0125UAA
125
125
99
100
Flange
CIMR-AU5A0145UAA
145
150
130
125
CIMR-AU5A0192UAA
192
200
172
150
Flange
CIMR-AU5A0242UAA
242
250
200
200
  1. Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
  2. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  3. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors

Back to Top

600V, Single-Phase Input, (575V Three-Phase Output)

Drive Model Number 1, 2, 3
Single Phase Input - Sizing Method A (A) (continuous full power)
Single Phase Input - Sizing Method B (B) (86% max power of connected motor size)
Without Additional Reactor
With Additional Reactor
Motor Amps Motor Size (HP) Motor Amps Motor Size (HP)
Motor Amps
Motor Size (HP)
CIMR-AU5A0003FAA
1.7
1
2.4
1.5
1.7
1
CIMR-AU5A0004FAA
2.4
1.5
2.7
2
2.7
2
CIMR-AU5A0006FAA
2.7
2
3.9
3
3.9
3
CIMR-AU5A0009FAA
3.9
3
6.1
5
6.1
5
CIMR-AU5A0011FAA
2.7
2
3.9
3
3.9
3
CIMR-AU5A0017FAA
6.1
5
6.1
5
9.0
7.5
CIMR-AU5A0022FAA
6.1
5
7.5
9.0
9.0
7.5
CIMR-AU5A0027FAA
9.0
7.5
11
10
11.0
10
CIMR-AU5A0032FAA
9.0
7.5
11
10
11.0
10
CIMR-AU5A0041FAA
17
15
17
15
22.0
20
CIMR-AU5A0052FAA
17
15
17
15
22.0
20
CIMR-AU5A0062FAA
27
25
27
25
32.0
30
CIMR-AU5A0077FAA
32
30
32
30
41
40
CIMR-AU5A0099FAA
32
30
32
30
41
40
CIMR-AU5A0125AAA
52
50
52
50
62
60
CIMR-AU5A0145AAA
52
50
52
50
62
60
CIMR-AU5A0192AAA
77
75
77
75
99
100
CIMR-AU5A0242AAA
77
75
77
75
99
100
  1. Standard Enclosure can be conventionally mounted, or heatsink external (kit required for models CIMR-AU2A0081FAA and smaller). Flange Enclosure includes special factory-installed gasketing and flange to provide NEMA 12 backside integrity when mounting heatsink external.
  2. Only models ending in FAA (CIMR-AU2A0211FAA and smaller) come standard with NEMA 1 End Cap Kits. Separately sold kits are available for larger models.
  3. For Flange Drives, use the sizing method above to determine proper drive size. Use selected model numbers with "UAA" suffix instead of "FAA" or "AAA" suffix.
  1. Use single phase input sizing method A for applications requiring more than 86% motor power. When sizing with additional reactor, refer to "Reactors for Single Phase Input" section of this price book. Caution: Adding more impedance than specified will degrade performance.
  2. Use single phase input sizing method B for applications requiring a maximum of 86% motor power.