200-240V, 3% Reactors | 200-240V, 5% Reactors | 380-480V, 3% Reactors | 380-480V, 5% Reactors | 500-600V, 3% Reactors | 500-600V, 5% Reactors

200-240V, 3% Line/Load Reactors

Rated Input Voltage
Nominal HP
Drive Model Number
Nominal 3% Impedance
Normal Duty
Heavy Duty
Reactor Rated Current (A)
Inductance (μH)
Enclosed Part Number
Weight (lb)
200-240V, 3-Phase
1/2
CIMR-AU2A0004
CIMR-AU2A0004
2
6000
URX000243
10
3/4
CIMR-AU2A0004
CIMR-AU2A0004
4
3000
05P00620-0020
11
200-240V, 3-Phase
1
CIMR-AU2A0006
CIMR-AU2A0006
4
3000
05P00620-0020
11
1.5
CIMR-AU2A0006
CIMR-AU2A0008
8
1500
05P00620-0027
14
200-240V, 3-Phase
2
CIMR-AU2A0008
CIMR-AU2A0008
8
1500
05P00620-0027
14
3
CIMR-AU2A0010
CIMR-AU2A0012
12
1250
05P00620-0032
16
200-240V, 3-Phase
5
CIMR-AU2A0018
CIMR-AU2A0021
18
800
05P00620-0036
16
7.5
CIMR-AU2A0021
CIMR-AU2A0030
25
500
05P00620-0041
29
200-240V, 3-Phase
10
CIMR-AU2A0030
CIMR-AU2A0040
35
400
05P00620-0046
32
15
CIMR-AU2A0040
CIMR-AU2A0056
45
300
05P00620-0050
41
200-240V, 3-Phase
20
CIMR-AU2A0056
CIMR-AU2A0069
55
250
05P00620-0054
42
25
CIMR-AU2A0069
CIMR-AU2A0081
80
200
05P00620-0058
43
200-240V, 3-Phase
30
CIMR-AU2A0081
--
80
200
05P00620-0058
43
30
--
CIMR-AU2A01101
80
200
05P00620-0058
43
200-240V, 3-Phase
40
CIMR-AU2A01101
CIMR-AU2A01381
100
150
URX000204
47
50
CIMR-AU2A01381
CIMR-AU2A01691
130
150
05P00620-0066
47
200-240V, 3-Phase
60
CIMR-AU2A01691
CIMR-AU2A02111
160
75
URX000206
59
75
CIMR-AU2A02111
CIMR-AU2A02501
250
45
URX000248
65
200-240V, 3-Phase
100
CIMR-AU2A02501
CIMR-AU2A03121
250
45
URX000248
65
125
CIMR-AU2A03121
CIMR-AU2A03601
320
40
URX000249
107
200-240V, 3-Phase
150
CIMR-AU2A03601
CIMR-AU2A04151
400
30
URX000250
111
175
CIMR-AU2A04151
CIMR-AU2A04151
500
25
URX000251
111
  1. A1000 chassis have a built-in DC link reactor equivalent to 3% line reactance. 240 VAC ratings are shown with 3% added AC reactance for 6% total.

Top
 

200-240V, 5% Line/Load Reactors

Rated Input Voltage
Nominal HP
Drive Model Number
Nominal 5% Impedance
Normal Duty
Heavy Duty
Reactor Rated Current (A)
Inductance (μH)
Enclosed Part Number
Weight (lb)
200-240V, 3-Phase
1/2
CIMR-AU2A0004
CIMR-AU2A0004
2
12000
05P00620-0015
11
3/4
CIMR-AU2A0004
CIMR-AU2A0004
4
6500
05P00620-0021
11
200-240V, 3-Phase
1
CIMR-AU2A0006
CIMR-AU2A0006
4
6500
05P00620-0021
11
1.5
CIMR-AU2A0006
CIMR-AU2A0008
8
3000
05P00620-0028
15
200-240V, 3-Phase
2
CIMR-AU2A0008
CIMR-AU2A0008
8
3000
05P00620-0028
15
3
CIMR-AU2A0010
CIMR-AU2A0012
12
2500
05P00620-0033
17
200-240V, 3-Phase
5
CIMR-AU2A0018
CIMR-AU2A0021
18
1500
05P00620-0037
15
7.5
CIMR-AU2A0021
CIMR-AU2A0030
25
1200
05P00620-0042
32
200-240V, 3-Phase
10
CIMR-AU2A0030
CIMR-AU2A0040
35
800
05P00620-0047
34
15
CIMR-AU2A0040
CIMR-AU2A0056
45
700
05P00620-0051
46
200-240V, 3-Phase
20
CIMR-AU2A0056
CIMR-AU2A0069
55
500
05P00620-0055
45
25
CIMR-AU2A0069
CIMR-AU2A0081
80
400
05P00620-0059
51
200-240V, 3-Phase
30
CIMR-AU2A0081
--
80
400
05P00620-0059
51
30
--
CIMR-AU2A01101
80
200
05P00620-0058
43
200-240V, 3-Phase
40
CIMR-AU2A01101
CIMR-AU2A01381
100
150
URX000204
47
50
CIMR-AU2A01381
CIMR-AU2A01691
130
100
05P00620-0066
47
200-240V, 3-Phase
60
CIMR-AU2A01691
CIMR-AU2A02111
160
75
URX000206
59
75
CIMR-AU2A02111
CIMR-AU2A02501
250
45
URX000248
65
200-240V, 3-Phase
100
CIMR-AU2A02501
CIMR-AU2A03121
250
45
URX000248
65
125
CIMR-AU2A03121
CIMR-AU2A03121
320
40
URX000249
107
200-240V, 3-Phase
150
CIMR-AU2A03601
CIMR-AU2A03121
400
30
URX000250
111
175
CIMR-AU2A04151
CIMR-AU2A03121
500
25
URX000251
111
  1. A1000 chassis have a built-in DC link reactor equivalent to 3% line reactance. 240 VAC ratings are shown with 3% added AC reactance for 6% total.

Top

380-480V, 3% Line/Load Reactors

Rated Input Voltage
Nominal HP
Drive Model Number
Nominal 3% Impedance
Normal Duty
Heavy Duty
Reactor Rated Current (A)
Inductance (μH)
Enclosed Part Number
Weight (lb)
380-480V, 3-Phase
1/2
CIMR-AU4A0002
CIMR-AU4A0002
1
18000
URX000242
11
3/4
CIMR-AU4A0002
CIMR-AU4A0002
2
12000
05P00620-0015
11
380-480V, 3-Phase
1
CIMR-AU4A0002
CIMR-AU4A0004
2
12000
05P00620-0015
11
1.5
CIMR-AU4A0004
CIMR-AU4A0004
4
6500
05P00620-0021
11
380-480V, 3-Phase
2
CIMR-AU4A0004
CIMR-AU4A0004
4
6500
05P00620-0021
11
3
CIMR-AU4A0005
CIMR-AU4A0005
8
3000
05P00620-0028
15
380-480V, 3-Phase
5
CIMR-AU4A0009
CIMR-AU4A00011
8
3000
05P00620-0028
15
7.5
CIMR-AU4A0011
CIMR-AU4A0018
12
2500
05P00620-0033
17
380-480V, 3-Phase
10
CIMR-AU4A0018
CIMR-AU4A0018
18
1500
05P00620-0037
19
15
CIMR-AU4A0023
CIMR-AU4A0031
25
1200
05P00620-0042
32
380-480V, 3-Phase
20
CIMR-AU4A0031
CIMR-AU4A0038
35
800
05P00620-0047
34
25
CIMR-AU4A0038
CIMR-AU4A0044
35
800
05P00620-0047
34
380-480V, 3-Phase
30
CIMR-AU4A0044
--
45
700
05P00620-0051
46
30
--
CIMR-AU4A00581
45
300
05P00620-0050
41
380-480V, 3-Phase
40
CIMR-AU4A00581
CIMR-AU4A00721
55
250
05P00620-0054
42
50
CIMR-AU4A00721
CIMR-AU4A00881
80
200
05P00620-0058
43
380-480V, 3-Phase
60
CIMR-AU4A00881
CIMR-AU4A00881
80
200
05P00620-0058
43
75
CIMR-AU4A01031
CIMR-AU4A01031
100
150
URX000204
47
380-480V, 3-Phase
100
CIMR-AU4A01391
CIMR-AU4A01651
130
100
05P00620-0066
47
125
CIMR-AU4A01651
CIMR-AU4A01651
160
75
URX000206
59
380-480V, 3-Phase
150
CIMR-AU4A02081
CIMR-AU4A02081
200
55
05P00620-0077
56
200
CIMR-AU4A02501
CIMR-AU4A02501
250
45
URX000248
65
380-480V, 3-Phase
250
CIMR-AU4A02961
CIMR-AU4A03621
320
40
URX000249
107
300
CIMR-AU4A03621
CIMR-AU4A04141
400
30
URX000250
111
380-480V, 3-Phase
350
CIMR-AU4A04141
CIMR-AU4A05151
500
25
URX000251
120
400
CIMR-AU4A05151
CIMR-AU4A06751
500
25
URX000251
120
380-480V, 3-Phase
450
CIMR-AU4A06751
CIMR-AU4A06751
600
20
URX000252
264
500
CIMR-AU4A06751
CIMR-AU4A06751
600
20
URX000252
264
380-480V, 3-Phase
600
CIMR-AU4A06751
CIMR-AU4A09301
750
15
URX000253
299
660
CIMR-AU4A09301
CIMR-AU4A09301
750
15
URX000253
299
380-480V, 3-Phase
700
CIMR-AU4A09301
CIMR-AU4A09301
900
13
URX000254
444
750
CIMR-AU4A09301
CIMR-AU4A12001
900
13
URX000254
444
380-480V, 3-Phase
800
CIMR-AU4A12001
CIMR-AU4A12001
1000
11
URX000244
479
900
CIMR-AU4A12001
CIMR-AU4A12001
1200
9
URX000246
584
380-480V, 3-Phase
1000
CIMR-AU4A12001
CIMR-AU4A12001
1200
9
URX000246
584
  1. A1000 chassis have a built-in DC link reactor equivalent to 3% line reactance. 240 VAC ratings are shown with 3% added AC reactance for 6% total.

Top

380-480V, 5% Line/Load Reactors

Rated Input Voltage
Nominal HP
Drive Model Number
Nominal 5% Impedance
Normal Duty
Heavy Duty
Reactor Rated Current (A)
Inductance (μH)
Enclosed Part Number
Weight (lb)
380-480V, 3-Phase
1/2
CIMR-AU4A0002
CIMR-AU4A0002
1
36000
URX000241
11
3/4
CIMR-AU4A0002
CIMR-AU4A0002
2
20000
05P00620-0016
11
380-480V, 3-Phase
1
CIMR-AU4A0002
CIMR-AU4A0004
2
20000
05P00620-0016
11
1.5
CIMR-AU4A0004
CIMR-AU4A0004
4
12000
05P00620-0023
13
380-480V, 3-Phase
2
CIMR-AU4A0004
CIMR-AU4A0004
4
12000
05P00620-0023
13
3
CIMR-AU4A0005
CIMR-AU4A0005
8
7500
URX000226
20
380-480V, 3-Phase
5
CIMR-AU4A0009
CIMR-AU4A00011
8
5000
05P00620-0029
18
7.5
CIMR-AU4A0011
CIMR-AU4A0018
12
4200
05P00620-0034
25
380-480V, 3-Phase
10
CIMR-AU4A0018
CIMR-AU4A0018
18
2500
05P00620-0038
34
15
CIMR-AU4A0023
CIMR-AU4A0031
25
1800
05P00620-0043
38
380-480V, 3-Phase
20
CIMR-AU4A0031
CIMR-AU4A0038
35
1200
05P00620-0048
48
25
CIMR-AU4A0038
CIMR-AU4A0044
35
1200
05P00620-0048
48
380-480V, 3-Phase
30
CIMR-AU4A0044
--
45
1200
05P00620-0052
57
30
--
CIMR-AU4A00581
45
700
05P00620-0051
46
380-480V, 3-Phase
40
CIMR-AU4A00581
CIMR-AU4A00721
55
500
05P00620-0055
45
50
CIMR-AU4A00721
CIMR-AU4A00881
80
400
05P00620-0059
51
380-480V, 3-Phase
60
CIMR-AU4A00881
CIMR-AU4A00881
80
400
05P00620-0059
51
75
CIMR-AU4A01031
CIMR-AU4A01031
100
300
05P00620-0062
55
380-480V, 3-Phase
100
CIMR-AU4A01391
CIMR-AU4A01651
130
200
05P00620-0067
61
125
CIMR-AU4A01651
CIMR-AU4A01651
160
150
05P00620-0073
68
380-480V, 3-Phase
150
CIMR-AU4A02081
CIMR-AU4A02081
200
110
05P00620-0078
72
200
CIMR-AU4A02501
CIMR-AU4A02501
250
90
05P00620-0083
107
380-480V, 3-Phase
250
CIMR-AU4A02961
CIMR-AU4A03621
320
75
05P00620-0088
129
300
CIMR-AU4A03621
CIMR-AU4A04141
400
60
05P00620-0092
145
380-480V, 3-Phase
350
CIMR-AU4A04141
CIMR-AU4A05151
500
50
05P00620-0096
262
400
CIMR-AU4A05151
CIMR-AU4A06751
500
50
05P00620-0096
262
380-480V, 3-Phase
450
CIMR-AU4A06751
CIMR-AU4A06751
600
40
05P00620-0100
319
500
CIMR-AU4A06751
CIMR-AU4A06751
600
40
05P00620-0100
319
380-480V, 3-Phase
600
CIMR-AU4A06751
CIMR-AU4A09301
750
29
05P00620-0104
349
660
CIMR-AU4A09301
CIMR-AU4A09301
750
29
05P00620-0104
349
380-480V, 3-Phase
700
CIMR-AU4A09301
CIMR-AU4A09301
900
25
URX000255
529
750
CIMR-AU4A09301
CIMR-AU4A12001
900
25
URX000255
529
380-480V, 3-Phase
800
CIMR-AU4A12001
CIMR-AU4A12001
1000
22
URX000245
567
900
CIMR-AU4A12001
CIMR-AU4A12001
1200
19
URX000247
599
380-480V, 3-Phase
1000
CIMR-AU4A12001
CIMR-AU4A12001
1200
19
URX000247
599
  1. A1000 chassis have a built-in DC link reactor equivalent to 3% line reactance. 240 VAC ratings are shown with 3% added AC reactance for 6% total.

Top

500-600V, 3% Line/Load Reactors

Rated Input Voltage
Nominal HP
Drive Model Number
Nominal 3% Impedance
Normal Duty
Heavy Duty
Reactor Rated Current (A)
Inductance (μH)
Enclosed Part Number
Weight (lb)
500-600V, 3-Phase
1/2
CIMR-AU5A0003
CIMR-AU5A0003
1
36000
URX000241
11
3/4
CIMR-AU5A0003
CIMR-AU5A0003
2
20000
05P00620-0016
11
500-600V, 3-Phase
1
CIMR-AU5A0003
CIMR-AU5A0003
2
20000
05P00620-0016
11
1.5
CIMR-AU5A0003
CIMR-AU5A0004
2
20000
05P00620-0016
11
500-600V, 3-Phase
2
CIMR-AU5A0003
CIMR-AU5A0004
4
9000
05P00620-0022
12
3
CIMR-AU5A0004
CIMR-AU5A0006
4
9000
05P00620-0022
12
500-600V, 3-Phase
5
CIMR-AU5A0006
CIMR-AU5A0009
8
5000
05P00620-0029
18
7.5
CIMR-AU5A0009
CIMR-AU5A0011
12
2500
05P00620-0033
17
500-600V, 3-Phase
10
CIMR-AU5A0011
CIMR-AU5A0017
12
2500
05P00620-0033
17
15
CIMR-AU5A0017
CIMR-AU5A0022
18
1500
05P00620-0037
19
500-600V, 3-Phase
20
CIMR-AU5A0022
CIMR-AU5A0027
25
1200
05P00620-0042
32
25
CIMR-AU5A0027
CIMR-AU5A0032
25
1200
05P00620-0042
32
500-600V, 3-Phase
30
CIMR-AU5A0032
--
35
800
05P00620-0047
34
30
--
CIMR-AU5A00411
35
400
05P00620-0046
32
500-600V, 3-Phase
40
CIMR-AU5A00411
CIMR-AU5A00521
45
300
05P00620-0050
41
50
CIMR-AU5A00521
CIMR-AU5A00621
55
250
05P00620-0054
42
500-600V, 3-Phase
60
CIMR-AU5A00621
CIMR-AU5A00771
80
200
05P00620-0058
43
75
CIMR-AU5A00771
CIMR-AU5A00991
80
200
05P00620-0058
43
500-600V, 3-Phase
100
CIMR-AU5A00991
CIMR-AU5A01251
100
150
URX000204
47
125
CIMR-AU5A01251
CIMR-AU5A01451
130
100
05P00620-0066
47
500-600V, 3-Phase
150
CIMR-AU5A01451
CIMR-AU5A01921
160
75
URX000206
59
200
CIMR-AU5A01921
CIMR-AU5A02421
200
55
05P00620-0077
56
500-600V, 3-Phase
250
CIMR-AU5A02421
--
250
45
05P00620-0077
65
  1. A1000 chassis have a built-in DC link reactor equivalent to 3% line reactance. 240 VAC ratings are shown with 3% added AC reactance for 6% total.

Top

500-600C, 5% Line/Load Reactors

Rated Input Voltage
Nominal HP
Drive Model Number
Nominal 5% Impedance
Normal Duty
Heavy Duty
Reactor Rated Current (A)
Inductance (μH)
Enclosed Part Number
Weight (lb)
500-600V, 3-Phase
1/2
CIMR-AU5A0003
CIMR-AU5A0003
1
18000
URX000242
11
3/4
CIMR-AU5A0003
CIMR-AU5A0003
2
32000
URX000227
11
500-600V, 3-Phase
1
CIMR-AU5A0003
CIMR-AU5A0003
2
32000
URX000227
11
1.5
CIMR-AU5A0003
CIMR-AU5A0004
2
32000
URX000227
11
500-600V, 3-Phase
2
CIMR-AU5A0003
CIMR-AU5A0004
4
12000
05P00620-0023
13
3
CIMR-AU5A0004
CIMR-AU5A0006
4
12000
05P00620-0023
13
500-600V, 3-Phase
5
CIMR-AU5A0006
CIMR-AU5A0009
8
7500
URX000226
20
7.5
CIMR-AU5A0009
CIMR-AU5A0011
12
4200
05P00620-0034
25
500-600V, 3-Phase
10
CIMR-AU5A0011
CIMR-AU5A0017
12
4200
05P00620-0034
25
15
CIMR-AU5A0017
CIMR-AU5A0022
18
2500
05P00620-0038
34
500-600V, 3-Phase
20
CIMR-AU5A0022
CIMR-AU5A0027
25
1800
05P00620-0043
38
25
CIMR-AU5A0027
CIMR-AU5A0032
25
1800
05P00620-0043
38
500-600V, 3-Phase
30
CIMR-AU5A0032
--
35
1200
05P00620-0048
48
30
--
CIMR-AU5A00411
35
800
05P00620-0047
34
500-600V, 3-Phase
40
CIMR-AU5A00411
CIMR-AU5A00521
45
700
05P00620-0051
46
50
CIMR-AU5A00521
CIMR-AU5A00621
55
500
05P00620-0055
45
500-600V, 3-Phase
60
CIMR-AU5A00621
CIMR-AU5A00771
80
400
05P00620-0059
51
75
CIMR-AU5A00771
CIMR-AU5A00991
80
400
05P00620-0059
51
500-600V, 3-Phase
100
CIMR-AU5A00991
CIMR-AU5A01251
100
300
05P00620-0062
55
125
CIMR-AU5A01251
CIMR-AU5A01451
130
200
05P00620-0067
61
500-600V, 3-Phase
150
CIMR-AU5A01451
CIMR-AU5A01921
160
150
05P00620-0073
68
200
CIMR-AU5A01921
CIMR-AU5A02421
200
110
05P00620-0078
72
500-600V, 3-Phase
250
CIMR-AU5A02421
--
250
90
05P00620-0083
107